DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 3-262 Device No. Function Set-point range Explanation S 3+1 Proportional gain (K ) P 0~30,000 (%) The proportion for magnifying/minifying the error between SV and PV. S 3+2 Integration gain (K) I 0~30,000 (%) The proportion for magnifying/minifying the integral value (The accumulated error). For control mode K0~K2, K5. Integral time constant (T) I 0~30,000 (ms) For control mode K10 S 3+3 Derivative gain (K ) D -30,000~30,000 (%) The proportion for magnifying/minifying the derivative value (The rate of change of the process error). For control mode K0~K2, K5.
Derivative time constant (T ) D -30,000~30,000 (ms) For control mode K10 S 3+4 Control mode 0: Automatic control 1: Forward control (E = SV - PV). 2: Reverse control (E = PV - SV). 5: Automatic mode with MV upper/lower bound control. When MV reaches upper/lower bound, the accumulation of integral value stops. 10: T / T mode with MV upper/lower bound control. I D When MV reaches upper/lower bound, the accumulation of integral value stops. S 3+5, 6 Tolerable range for error (E), 32-bit 0~2,147,483,647 E = the error between SV and PV. If S 3 +5 is set as 5, when E is between -5 and 5, E will be 0. When S 3 +5 = K0, the function will not be enabled.
S 3+7, 8 Upper bound of output value (MV) , 32-bit -2,147,483,648~ 2,147,483,647 Ex: if S 3+6 is set as 1,000, MV will be 1,000 when it exceeds 1,000. S 3+6 has to be bigger or equal to S 3+7, otherwise the upper bound and lower bound value will switch S 3+9, 10 Lower bound of output value (MV) , 32-bit -2,147,483,648~ 2,147,483,647 Ex: if S 3+7 is set as -1,000, MV will be -1,000 when it is smaller than -1,000. S 3+11, 12 Upper bound of integral value, 32-bit -2,147,483,648~ 2,147,483,647 Ex: if S 3+8 is set as 1,000, the integral value will be 1,000 when it is bigger than 1,000 and the integration will stop.
S 3+8 has to be bigger or equal S 3 +9; otherwise the upper bound and lower bound value will switch. S 3+13, 14 Lower bound of integral value, 32-bit -2,147,483,648~ 2,147,483,647 Ex: if S 3+9 is set as -1,000, the integral value will be -1,000 when it is smaller than -1,000 and the integration will stop. S 3+15, 16 Accumulated integral value, 32-bit Available range of 32-bit floating point The accumulated integral value is usually for reference. Users can clear or modify it (in 32-bit floating point) according to specific needs.