Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 12. The explanation of 32-bit S 3 and 16-bit S 3 are almost the same. The difference is the capacity of S 3 +5 ~ S 3 +20. PID Equations: 1. When control mode ( S 3 +4) is selected as K0, K1, K2 and K5:  In this control mode, PID operation can be selected as Automatic, Forward, Reverse and Automatic with MV upper/lower bound control modes. Forward / Reverse direction is designated in S 3 +4. Other relevant settings of PID operation are set by the registers designated in S 3 ~ S 3 +5.  PID equation for control mode k0~k2:    S t PV K S t E K t E K MV D I P * 1 * *    where MV : Output value P K : Proprotional gain  t E : Error value PV (t) :

Present measured value SV (t) : Target value D K : Derivative gain  S t PV : Derivative value of PV(t) I K : Integral gain  S t E 1 : Integral value of E(t)  When ( ) t E is smaller than 0 as the control mode is selected as forward or inverse, ( ) t E will be regarded as “0"  Control diagram: In diagram below, S is derivative operation, referring to “(PV ﹣ previous PV) ч sampling time”. 1 / S is integral operation, referring to “previous integral value + (error value Ч sampling time)”. G(S) refers to the device being controlled. 3-263 Device No.

Function Set-point range Explanation S 3+17, 18 The previous PV, 32-bit -2,147,483,648~ 2,147,483,647 The previous PV is usually for reference. Users can clear or modify it according to specific needs. S 3+19, 20 For system use only. Control mode PID equation Forward, automatic E(t) = SV – PV Inverse E(t) = PV – SV