DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming PID operation is within dotted area The equation above illustrates that this operation is different from a general PID operation on the application of the derivative value. To avoid the fault that the transient derivative value could be too big when a general PID instruction is first executed, our PID instruction monitors the derivative value of the PV. When the variation of PV is excessive, the 2. When control mode ( S 3 +4) is selected as K3 and K4: instruction will reduce the output of MV/. The equation is exclusively for temperature control will be modified as:
S t E K S t E K t E K MV D I P * 1 1 1 , where t PV - t SV t E Control diagram: In diagram below, 1/K I and 1/K P refer to “divided by K I ” and “divided by K P ”. Because this mode is exclusively for temperature control, users have to use PID instruction together with GPWM instruction. See Application 3 for more details PID operation is within dotted area This equation is exclusively designed for temperature control. Therefore, when the sampling time (T S ) is set as 4 seconds (K400), the range of output value (MV) will be K0 ~ K4,000 and the cycle time of GPWM instruction used together has to be set as 4 seconds (K4000) as well.
3-264 1/S K I + + + K P + K D S G(s) 1/S 1/K I + + + 1/K P + S K D 1/K P G(s)