Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set  If users have no idea on parameter adjustment, select K3 (auto-tuning). After all the parameters are adjusted (the control direction will be automatically set as K4), users can modify the parameters to better ones according to the adjusted results. 3. When control mode ( S 3 +4) is selected as K10:  S 3 +2 (K I ) and S 3 +3 (K D ) in this mode will be switched to parameter settings of Integral time constant (T I ) and Derivative time constant (T D ).  When output value (MV) reaches the upper bound, the accumulated integral value will not increase. Also, when MV reaches the lower bound, the accumulated integral value will not decrease.

 The equation for this mode will be modified as:       t E dt d T dt t E T t E K MV D I P 1       Where    t PV - t SV t E  Control diagram: PID operation is within dotted area Notes and suggestion: 1. S 3 + 3 can only be the value within 0 ~ 30,000. 2. There are a lot of circumstances where PID instruction can be applied; therefore, please choose the control functions appropriately. For example, when users select parameter auto-tuning for the temperature ( S 3 + 4 = K3), the instruction can not be used in a motor control environment otherwise improper control may occur. 3.

When you adjust the three main parameters, K P , K I and K D ( S 3 + 4 = K0 ~ K2), please adjust K P first (according to your experiences) and set K I and K D as 0. When the output can roughly be controlled, proceed to increase K I and K D (see example 4 below for adjustment methods). K P = 100 refers to 100%, i.e. the proportional gain to the error is 1. K P and K P > 100% will increase the error 4. When temperature auto-tuning function is selected( S 3 + 4 = K3, K4), it is suggested that store the parameters in D register in latched area in case the adjusted parameters will disappear after 3-265 1/S 1/T I + + + K P + S T D G(s)