Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming the power is cut off. There is no guarantee that the adjusted parameters are suitable for every control requirement. Therefore, users can modify the adjusted parameters according to specific needs, but it is suggested to modify only K I or K D. 5. PID instruction has to be controlled with many parameters; therefore care should be taken when setting each parameter in case the PID operation is out of control. Example 1: Block diagram of application on positioning ( S 3 +4 = 0) Position instruction (SV) PID Example 2:

Block diagram of application on AC motor drive ( S 3 +4 = 0) S+MV Speed instruction (S) AC motor drive Acceleration/deceleration output (MV) Acceleration/deceleration instruction (SV) Speed detection device (P) PID Actual acceleration/ deceleration speed (PV = S - P) Example 3: Block diagram of application on temperature control ( S 3 +4 = 1) PID Temperature instruction (SV) Heating (MV) Heater Actual temperature (PV) Temperature detection device Example 4: PID parameters adjustment Assume that the transfer function of the controlled device G(S) in a control system is a first-order function  a s b s G   (model of general motors), SV = 1, and sampling time (T S ) = 10ms.

Suggested steps for adjusting the parameters are as follows: Step1: Set K I and K D as 0, and K P as 5, 10, 20, 40. Record the SV and PV respectively and the results are as the figure below. 3-266 MV Controlled device Encoder