3. Instruction Set 1.5 K =40 P K =20 P K =10 P SV=1 1 K =5 P 0.5 00 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Time (sec) Step 2: When K P is 40, response overshoot occurs, so we will not select it. When K P is 20, PV response is close to SV and won’t overshoot, but transient MV will be to large due to a fast start-up. We can put it aside and observe if there are better curves. When K P is 10, PV response is close to SV and is smooth. We can consider using it. When K P is 5, the response is too slow. So we won’t use it. Step 3: Select K P = 10 and increase K I gradually, e.g. 1, 2, 4, 8. K I should not be bigger than K P . Then, increase K D as well, e.g. 0.01, 0.05, 0.1, 0.2.
K D should not exceed 10% of K P . Finally we obtain the figure of PV and SV below. 1.5 PV=SV 1 0.5 K =10,K =8,K =0.2 P I D Time (sec) 00 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 of the actual control system. Note: The example is only for reference. Users have to adjust parameters according to the condition Example 5: Transition between the manual mode (K7) and the automatic mode (K5) If the setting of the PID parameters is complete, and the control mode is the manual mode (K7), the control curve will be as shown below. 3-267