DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming If the control mode becomes the automatic mode (K5), the output value MV changes from the output value set by users to the output value of the PID operation. Example 6: Transition between the manual mode (K8) and the automatic mode (K5) If the setting of the PID parameters is complete, and the control mode is the manual mode (K8), the control curve will be as shown below. If the control mode becomes the automatic mode (K5), the accumulated integral value will be the integral value converted from the last MV, and the accumulated integral value will be converted into the output value of the PID operation.
The program for example 5 and program 6 are shown below. In the figure below, ,M0 is a flag for enabling the instruction PID. When M1 is On, the manual mode is used. When M1 is Off, the automatic mode is used. Application 1: PID instruction in pressure control system. (Use block diagram of example 1) Control purpose: Enabling the control system to reach the target pressure. 3-268