3. Instruction Set Control properties: The system requires a gradual control. Therefore, the system will be overloaded or out of control if the process progresses too fast. Solution 1: Longer sampling time Suggested solution: Solution 2: Using delay instruction.
See the figure below 0 0rpm 0 0V 511 rpm 3000 255 5V Pressure SV (D0) Set value ramp up MV converted to speed SV PID MV D5 Speed converted to voltage AC motor drive PV D1 D1116 Wave A Wave B pressure meter Voltage converted to SV D1110 0 0V 511 10V SV SV D2 stores increased value of each shift D3 stores the time interval of each shift 280 280 250 200 150 100 50 Values in can modify D2 and D3 according to actual requirement 0 0 Wave A Wave B t t 3-269