Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 0 M3 M2=ON 255 D40 + D32 D1116 speed convert to voltage AC drive SV of speed D30 D31 + 0rpm 3000rpm MV convert to accel/decel D1 SV D0 SV ramp-up (optional) D1110 M0=ON PV MV D5 pressure meter SV of pressure PID M1=ON Part of the example program: M1002 M0 M1 M3 M2 K3000 D32 > K0 D32 K255 D32 > M1 Application 3: Using auto-tuning for temperature control Control purpose: Calculating optimal parameter of PID instruction for temperature control Control properties: Users may not be familiar with a new temperature environment. In this case, selecting auto-tuning ( S 3 +4 = K3) for an initial adjustment is suggested.

After initial tuning is completed, the instruction will auto modify control mode to the mode exclusively for adjusted temperature ( S 3 +4 = K4). In this 3-271 MOV K1000 D40 MOV D0 D1 MOV K0 D5 MOV D40 D30 ADD D30 D31 D32 MOV K3000 D32 MOV K0 D32 DIV D32 K11 D32 MOV K255 D32 MOV D32 D1116 PID D1 D1110 D10 D5