Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Registers for received data (responding messages) Program Example 2: Communication between PLC and VFD-B series AC motor drives (RTU Mode, M1143 = ON) M1002 Set communication protocol as 9600, 8, E, 1 Retain communication protocol Set receiving timeout as 100ms Set as RTU mode X1 Sending request X0 Set communication instruction: Data address: H2000 Write in data H12 Device address: 01 M1127 The receiving data is stored in D1070~D1085 in Hex. Process of receiving data Receiving completed Reset M1127 PLC  VFD-B, PLC transmits: 01 06 2000 0012 02 07 VFD-B  PLC, PLC receives:

01 06 2000 0012 02 07 3-293 Register Data Descriptions D1070 low ‘0’ 30 H ADR 1 ADR 0 D1070 high ‘1’ 31 H D1071 low ‘0’ 30 H CMD 1 CMD 0 D1071 high ‘6’ 36 H D1072 low ‘0’ 30 H Data address D1072 high ‘1’ 31 H D1073 low ‘0’ 30 H D1073 high ‘0’ 30 H D1074 low ‘1’ 31 H Data content D1074 high ‘7’ 37 H D1075 low ‘7’ 37 H D1075 high ‘0’ 30 H D1076 low ‘7’ 37 H LRC CHK 1 LRC CHK 0 D1076 high ‘1’ 31 H MOV H87 D1120 SET M1120 MOV K100 D1129 SET M1143 SET M1122 MODWR K1 H2000 H12 RST M1127