DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Registers for data to be sent (sending messages) Registers for received data (responding messages) Program Example 3: 1. In the communication between PLC and VFD-B series AC motor drive (ASCII Mode, M1143 = OFF), executes Retry when communication time-out, data receiving error or parameter error occurs 2. When X0 = ON, PLC will write data H1770 (K6000) into address H0100 in device 01 (VFD-B). 3. M1129 will be ON when communication time-out occurs. The program will trigger M1129 and send request for reading the data again. 4. M1140 will be ON when data receiving error occurs.
The program will trigger M1140 and send request for reading the data again. 5. M1141 will be ON when parameter error occurs. The program will trigger M1141 and send request for reading the data again.
3-294 Register Data Descriptions D1089 low 01 H Address of AC motor drive D1090 low 06 H Command code of AC motor drive D1091 low 20 H Data address D1092 low 00 H D1093 low 00 H Data content D1094 low 12 H D1095 low 02 H CRC CHK Low D1096 low 07 H CRC CHK High Register Data Descriptions D1070 low 01 H Address of AC motor drive D1071 low 06 H Command code of AC motor drive D1072 low 20 H Data address D1073 low 00 H D1074 low 00 H Data content D1075 low 12 H D1076 low 02 H CRC CHK Low D1077 low 07 H CRC CHK High