DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming M1002 Set up communication protocol as 9600, 7, E, 1 Retain communication protocol Set up communication time-out: 100ms X0 M1129 Sending request X0 Communication instruction setting: Device address: 1 K0: Reserved Receiving completed M1127 Processing received data Reset M1127. PLC VFD, PLC sends: “: 01 06 2002 0002 D5 ” VFD PLC, PLC sends: “: 01 06 2002 0002 D5 ” Data to be sent (sending messages): 3-306 MOV H86 D1120 SET M1120 MOV K100 D1129 SET M1122 RSTEF K1 K0 RST M1127 Data Descriptions ‘0’ 30 H ADR 1 ADR 0 AC drive address : ADR (1,0) ‘1’ 31 H ‘0’ 30 H CMD 1 CMD 0 Command code:
CMD (1,0) ‘6’ 36 H ‘2’ 32 H Data address ‘0’ 30 H ‘0’ 30 H ‘2’ 32 H ‘0’ 30 H Data contents ‘0’ 30 H ‘0’ 30 H ‘2’ 32 H ‘D’ 44 H LRC CHK 1 LRC CHK 0 Error checksum: LRC CHK (0,1) ‘5’ 35 H