Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 106 Operands: S : Address of communication device n : Operation mode Explanations: 2. M1177= ON, RSTEF instruction supports COM2(RS-485), COM3(RS-485). 1. M1177 = OFF (Default), RSTEF instruction supports COM2(RS-485). 3. M1177 has to be set up in advance for selecting the target model of VFD. When M1177 = OFF (Default), RSTEF instruction supports Delta’s VFD-A inverter. When M1177 = ON, these instructions support other models of VFD inverters, e.g. VFD-B, VFD. 4. There is no limitation on the times of using RSTEF instruction, however only one instruction can be executed on single COM port at a time. 5.

If rising-edge (LDP, ANDP, ORP) or falling-edge (LDF, ANDF, ORF) contacts are used before RSTEF instruction, sending request flags M1122 (COM2) / M1316 (COM3) has to be enabled in advance for obtaining correct operation. 6. For detailed information of associated flags and special registers, please refer to RS instruction. 7. M1177 = OFF, only Delta VFD-A is supported and the definition of each operand is: a) S 1 = Address of VFD-A. Range of S 1 : K0 ~ K31 b) n = Communication mode. Range: K1 ~ K2. n = 1: communicate with VFD at designated address. n = 2: communicate with all connected VFDs. .

c) RSTEF is a handy communication instruction used for reset when errors occur in AC motor drive operation. d) The feedback data from the peripheral equipment will be stored in D1070 ~ D1080. When n = 2, PLC will not receive any data. 8. M1177 = ON, other Delta VFDs are supoported  S 1 = Address of VFD. Range of S 1 : K0 ~ K255, when S 1 is specified as K0, PLC will broadcast to all connected VFDs Program Example: COM2 (RS-485) Communication between PLC and VFD-B series AC motor drives (ASCII Mode, M1143 = OFF). Retry when communication time-out occurs.

3-305 Mnemonic Operands Function Controllers RSTEF Reset Abnormal VFD ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F RSTEF: 5 steps S * * * n * * * 16-bit 32-bit SA2 SA2 SA2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE