DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Received data (responding messages) 3-304 Data Descriptions ‘0’ 30 H ADR 1 ADR 0 ‘1’ 31 H ‘0’ 30 H CMD 1 CMD 0 ‘3’ 33 H ‘0’ 30 H Number of data (count by byte) ‘A’ 41 H ‘0’ 30 H Content of address 2100 H PLC automatically converts ASCII codes and store the converted value in D1070 = 00C8 H ‘0’ 30 H ‘C’ 43 H ‘8’ 38 H ‘7’ 37 H Content of address 2101 H PLC automatically converts ASCII codes and store the converted value in D1071 = 7C08 H ‘C’ 43 H ‘0’ 30 H ‘8’ 38 H ‘3’ 33 H Content of address 2102 H PLC automatically converts ASCII codes and store the converted value in D1072 = 3E00 H ‘E’ 45 H ‘0’ 30 H ‘0’ 30 H ‘9’ 39 H Content of address 2103H PLC automatically converts ASCII codes and store the converted value in D1073 = 93AB H ‘3’ 33 H ‘A’ 41 H ‘B’ 42 H ‘0’ 30 H Content of address 2104 H PLC automatically converts ASCII codes and store the converted value in D1074 = 0000 H ‘0’ 30 H ‘0’ 30 H ‘0’ 30 H ‘2’ 32 H LRC CHK 1 LRC CHK 0 ‘A’ 41 H