Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set user manual of specific VFD for details.) and store the feedback data in D1070~D1074. However, the content in D1070~D1074 will not be updated when receiving error or timeout occurs. Therefore, please check the status of receiving completed flag before applying the received data Program Example: COM2 (RS-485) 1. Communication between PLC and VFD-B series inverter (ASCII Mode, M1143 = OFF). Retry when communication time-out occurs. 2. Read VFD status at parameter address 2100H~2104H and store the received data in D1070 ~ D1074. M1002 Set up communication protocol as 9600, 7, E, 1 Retain communication protocol Set up communication time-out:

100ms M1129 X0 Sending request Retry when communication time-out occurs X0 Communication instruction setting: Device address: 1 K0: Reserved Receiving completed M1127 Processing received data The received data is stored in D1070 ~ D1074. Reset M1127. PLC  VFD-B, PLC sends: “ :01 03 2100 0005 D6 ” VFD-B  PLC, PLC receives: “:01 03 0A 00C8 7C08 3E00 93AB 0000 2A ” Data to be sent (sending messages) 3-303 MOV H86 D1120 SET M1120 MOV K100 D1129 SET M1122 RDST K1 K0 RST M1127 Data Descriptions ‘0’ 30 H ADR 1 ADR 0 AC drive address : ADR (1,0) ‘1’ 31 H ‘0’ 30 H CMD 1 CMD 0 Command code:

CMD (1,0) ‘3’ 33 H 2’ 32 H Starting data address ‘1’ 31 H ‘0’ 30 H ‘0’ 30 H ‘0’ 30 H Number of data (count by word) ‘0’ 30 H ‘0’ 30 H ‘5’ 35 H ‘D’ 44 H LRC CHK 1 LRC CHK 0 Error checksum: LRC CHK (0,1) ‘6’ 36 H