Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 8. M1177 = ON, other Delta VFDs are supoported a) Range of S 1 : K1 ~ K255 b) The instruction will read VFD status at parameter address 2100H~2104H (Please refer to 3-302 Feedback Explanation Data storage Nn = “00” Frequency command = ABC.D (Hz) Nn = “01” Output frequency = ABC.D (Hz) Nn = “02” Output current = ABC.D (A) PLC will automatically convert the ASCII characters ”ABCD” into D1050. For example, ”ABCD” = “0600”, PLC will convert ABCD into K0600 (0258 H) and store it in the special register D1050.

Nn = “03” Operation command ‘A’ = ‘0’ Stop, ‘5’ JOG (forward) ‘1’ Forward operation ‘6’ JOG (reverse) ‘2’ Stop, ‘7’ JOG (reverse) ‘3’ Reverse operation ‘8’ Abnormal ‘4’ JOG (forward), PLC will automatically convert the ASCII character in ”A” into D1051. For example, ”A” = “3”, PLC will convert A into K3 and store it in the special register D1051.

‘B’ = b7 b6 b5 b4 Frequency reference source 0 0 0 0 Digital keypad 0 0 0 1 1st Step Speed 0 0 1 0 2nd Step Speed 0 0 1 1 3rd Step Speed 0 1 0 0 4th Step Speed 0 1 0 1 5th Step Speed 0 1 1 0 6th Step Speed 0 1 1 1 7th Step Speed 1 0 0 0 JOG frequency 1 0 0 1 Analog input frequency command 1 0 1 0 RS-485 communication interface 1 0 1 1 Up/Down control b3 = 0 Non-DC braking stop 1 DC braking stop b2 = 0 Non-DC braking start 1 DC braking start b1 = 0 Forward 1 Reverse b0 = 0 Stop 1 Run PLC will store bit status of ”B” in special auxiliary relay M1168 (b0) ~ M1175 (b7).

“CD” = “00” No error “10” OcA “01” oc “11” Ocd “02” ov “12” Ocn “03” oH “13” GFF “04” oL “14” Lv “05” oL1 “15” Lv1 “06” EF “16” cF2 “07” cF1 “17” bb “08” cF3 “18” oL2 “09” HPF “19” PLC will automatically convert the ASCII characters in ”CD” into D1052. For example, ”CD” = “16”, PLC will convert CD into K16 and store it in the special register D10512