Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Program Example: Connect PLC to VFD series AC motor drive (RTU mode, M1143 = ON), (8-bit mode, M1161 = ON), Write the data to be sent (H1770) into address H0706 on VFD. M1002 Set communication protocol as 9600,7,E,1 Retain communication setting Set communication timeout as: 100ms Sending request pulse 8-bit mode Write data to be sent in advance Sending request X0 M1123 Receiving completed Processing received data Reset M1123 PLC  VFD, PLC sends: 01 06 0706 1770 66 AB Registers for sent data (sending messages) The error checksum CRC CHK (0,1) can be calculated by CRC instruction (8-bit mode, M1161 = ON). M1000 CRC checksum:

66 H is stored in low byte of D106 and AB H in low byte of of D107, 3-312 MOV H86 D1120 SET M1120 MOV K100 D1129 SET M1161 SET M1122 RS D100 K8 D120 K8 RST M1123 Register Data Explanation D100 low byte 01 H Address D101 low byte 06 H Function D102 low byte 07 H Data address D103 low byte 06 H D104 low byte 17 H Data content D105 low byte 70 H D106 low byte 66 H CRC CHK 0 D107 low byte AB H CRC CHK 1 CRC D100 K6 D106