Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set API 110 Operands: S 1 : 1 st comparison value S 2 : 2 nd comparison value D : Comparison result, 3 consecutive devices Explanations: 1. The data of S 1 is compared to the data of S 2 and the result ( > , = , < ) is indicated by three bit devices in D . 2. If the source operand S 1 or S 2 is specified as constant K or H, the integer value will automatically be converted to binary floating point for comparison. Program Example: 1. If the specified device is M10, M10~M12 will automatically be used. 2. When X0 = ON, one of M10~M12 will be ON. When X0 = OFF, DECMP is not executed, M10~M12 will retain their previous state before X0 = OFF. 3.

Connect M10~M12 in series or parallel for achieving the results of , , ≠. ≧≦ 4. RST or ZRST instruction is required if users need to reset the comparison result. X0 M10 M10 = ON when (D1,D0)>(D101,D100) M11 M12 M11 = ON when (D1,D0)=(D101,D100) M12 = ON when (D1,D0) 3-313 Mnemonic Operands Function Controllers D ECMP P Floating point compare ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F DECMP, DECMPP: 13 steps S 1 * * * S 2 * * * D * * * PULSE 16-bit 32-bit SA2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE DECMP D0 D100 M10