3. Instruction Set Registers for received data (responding messages) RTU mode (M1143 = ON) When X0 = ON, MODRW instruction executes the function specified by Function Code H10 PLC VFD-B,PLC transmits: “01 10 2000 0002 04 1770 0012 EE 0C” VFD-B PLC, PLC receives: ”01 10 2000 0002 4A08” Registers for data to be sent (sending messages) 3-387 Register Data Descriptions D1264 Low byte ‘7’ 37 H D1264 High byte ‘0’ 30 H D1265 Low byte ‘0’ 30 H Data contents 2 The content of register D51:
H0012(K18) D1265 High byte ‘0’ 30 H D1266 Low byte ‘1’ 31 H D1266 High byte ‘2’ 32 H D1267 Low byte ‘3’ 33 H LRC CHK 1 LRC CHK 0 LRC CHK (0,1) is error check D1267 High byte ‘0’ 30 H Register Data Descriptions D1070 Low byte ‘0’ 30 H ADR 1 ADR 0 D1070 High byte ‘1’ 31 H D1071 Low byte ‘1’ 31 H CMD 1 CMD 0 D1071 High byte ‘0’ 30 H D1072 Low byte ‘2’ 32 H Data Address D1072 High byte ‘0’ 30 H D1073 Low byte ‘0’ 30 H D1073 High byte ‘0’ 30 H D1074 Low byte ‘0’ 30 H Number of Register D1074 High byte ‘0’ 30 H D1075 Low byte ‘0’ 30 H D1075 High byte ‘2’ 32 H D1076 Low byte ‘C’ 43 H LRC CHK 1 LRC CHK 0 D1076 High byte ‘D’ 44 H Register Data Descriptions D1256 Low byte 01 H Address D1257 Low byte 10 H Function D1258 Low byte 20 H Data Address D1259 Low byte 00 H D1260 Low byte 00 H Number of Register D1261 Low byte 02 H D1262 Low byte 04 H Byte Count D1263 Low byte 17 H Data content 1 The content of D50:
H1770 (K6000) D1264 Low byte 70 H D1265 Low byte 00 H Data content 2 The content of D51: H0012 (K18) D1266 Low byte 12 H D1262 Low byte EE H CRC CHK Low D1263 Low byte 0C H CRC CHK High