DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Registers for received data (responding messages) Program example 12: COM1 (RS-232) / COM3 (RS-485), Function Code H10 1. Function code K16 (H10): Write in multiple Word devices. Up to 16 Words can be written. For PLC COM2 ASCII mode, only 8 words can be written. 2. PLC COM1/COM3 will not process the received data 3. Take the connection between PLC COM3 and VFD-B for example, the tables below explain the status when PLC COM3 writes multiple Words in VFD-B. (M1320 = OFF, ASCII mode) (M1320 = ON, RTU mode) If PLC applies COM1 for communication, the below program can be usable by changing: 1. D1109→D1036: communication protocol 2.
M1136→M1138: retain communication setting 3. D1252→D1249: Set value for data receiving timeout 4. M1320→M1139: ASCII/RTU mode selection 5. M1316→M1312: sending request 6. M1318→M1314: receiving completed flag 3-388 Register Data Descriptions D1070 Low byte 01 H Address D1071 Low byte 10 H Function D1072 Low byte 20 H Data Address D1073 Low byte 00 H D1074 Low byte 00 H Number of Register D1075 Low byte 02 H D1076 Low byte 4A H CRC CHK Low D1077 Low byte 08 H CRC CHK High