3. Instruction Set Operands: S : Pulse output frequency D 1 : Pulse output device (Y0, Y2) D 2 : Direction signal output Explanations: 1. The instruction only supports the pulse output type: Pulse + Direction. 2. S is the designated pulse output frequency. Available range: -100,000Hz ~ +100,000 Hz. “+/-” signs indicate forward/reverse output direction. The frequency can be changed during pulse output. However, if the specified output direction is diferent from the current output direction, the instruction will stop for 1 scan cycle then restart with the changed frequency. 3. D 1 is the pulse output device. It can designate CH0(Y0) and CH1(Y2). 4. D 2 is the direction signal output device.
It can designate CH0(Y1) and CH1(Y3). 5. The operation of D 2 corresponds to the “+” or “-“ of S . When S is “+”, D 2 will be OFF; when S is “-“, D 2 will be ON. 6. M1305 and M1306 can change the output direction of CH0/CH1 set in D 2 . When S is “-“, D 2 will be ON, however, if M1305/M1306 is set ON before instruction executes, D 2 will be OFF during execution of instruction. 7. PLSV instruction does not support settings for ramp up or ramp down. If ramp up/down process is required, please use API 67 RAMP instruction. 8. If the drive contact turns off during pulse output process, pulse output will stop immediately. Program Example: When M10 = ON, Y0 will output pulses at 20kHz.
Y1 = OFF indicates forward direction. M10 3-405 API Mnemonic Operands Function Controllers 157 D PLSV Adjustable Speed Pulse Output ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word Devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F PLSV: 7 steps DPLSV: 13 steps S * * * * * * * * * * * D 1 * D 2 * * * PULSE 16-bit 32-bit SA2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE DPLSV K20000 Y0 Y1