DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming API 192 Operands: S 1 : Number of output pulses on X axis S 2 : Number of output pulses on Y axis S : Max. point to point output frequency D : Pulse output device Explanations: 1. For ES2/EX2 models, only V1.20 or above supports the function. 3. S 1 and S 2 specify the number of output pulses (absolute positioning) on X axis (Y0) and Y axis 2. The instruction only supports the pulse output type: Pulse / Direction. (Y2). Range: -2,147,483,648 ~ +2,147,483,647 (The “+/-“ sign indicates the forward/backward direction).
In forward direction, the present value of pulse output on CH0 (D1031 High, D1030 low), CH1 (D1337 high, D1336 low) increases. In reverse direction pulse output, value in (D1031, D1330) and (D1336, D1337) decreases. 4. D can designate Y0 only. Y0 is the pulse output point of X axis; Y1 is the direction signal output of X axis.(OFF: positive; ON: negative) Y2 is the pulse output point of Y axis; 5. For the rest of the explanations on the instruction, special D and special M, please refer to API Y3 is the direction signal output of Y axis (OFF: positive; ON: negative) 191 DPPMR instruction. Program Example: 1. Draw a rhombus as the figure below.
Y (0,0) X (-27000,-27000) (27000,-27000) (0,-55000) 3-460 Mnemonic Operands Function 2-Axis Absolute Point to Point Motion Controllers D PPMA ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F DPPMA: 17 steps S 1 * * * S 2 * * * S * * * D * PULSE 16-bit 32-bit SA2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE