Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Operands: S 1 : Source device 1 S 2 : Source device 2 Explanation: 1. This instruction conducts logic operation between the content in S 1 and S 2 . If the result is not “0”, the continuity of the instruction is enabled. If the result is “0”, the continuity of the instruction is disabled. 2. OR# ( #: &, |, ^) instruction is used for parallel connection with contacts. 3. Operation: & : Logic “AND” operation, | : Logic “OR” operation, ^ : Logic “XOR” operation 4. When 32-bit counters (C200 ~ C254) are used in this instruction, make sure to adopt 32-bit instruction (DOR#).

If 16-bit instruction (OR#) is adopted, a “program error” will occur and the ERROR indicator on the MPU panel will flash Program Example: M60 will be ON either when both X2 and M30 are “ON”, or 1: the result of logical OR operation between D10 and D20 ≠ 0, or 2: the result of logical XOR operation between CD100 and D200 ≠ 0. X2 M30 M60 3-501 API Mnemonic Operands Function Controllers 221~ 223 D OR# Parallel Type Logic Operation ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F OR#: 5 steps DOR#:

9 steps S 1 * * * * * * * * * * * S 2 * * * * * * * * * * * PULSE 16-bit 32-bit ES2/ EX2 SS2 SA2/ SE SX2 ES2/ SA2/ ES2/ SA2/ SS2 SX2 SS2 SX2 EX2 SE EX2 SE 16 -bit 32 -bit Continuity Discontinuity API No. instruction instruction condition condition 221 OR& DOR& S 1 & S 2≠0 S 1 & S 2=0 222 OR| DOR| S 1 | S 2≠0 S 1 | S 2=0 223 OR^ DOR^ S 1 ^ S 2≠0 S 1 ^ S 2=0 OR | D10 D20 OR ^ D100 D200