Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Operands: Explanations: S 1 : Source device 1 S 2 : Source device 2 1. This instruction compares the content in S 1 and S 2 . Take “FLD=” for example, if the result is “=”, the continuity of the instruction is enabled. If the result is “≠”, the continuity of the instruction is disabled. 2. The user can specify the floating point value directly into operands S 1 and S 2 (e.g. F1.2) or store the floating point value in D registers for further operation. 3. FLD ※ instruction is used for direct connection with left hand bus bar. Program Example: When the content in D200(D201) ≤ F1.2 and X1 is ON, Y21 = ON and latched.

X1 3-515 API Mnemonic Operands Function Controllers ES2/EX2 SS2 SA2 SX2 SE Controllers 275~ 280 FLD※ Floating Point Contact Type Comparison LD※ ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F FLD※: 9 steps S 1 * * * S 2 * * * PULSE 16-bit 32-bit ES2/ EX2 SS2 SA2/ SE SX2 ES2/ EX2 SS2 SA2/ SE SX2 ES2/ SA2/ SS2 SX2 EX2 SE API No. 32 -bit instruction Continuity condition Discontinuity condition 275 FLD= S 1=S 2 S 1≠S 2 276 FLD> S 1>S 2 S 1≦S 2 277 FLD< S 1<S 2 S 1≧S 2 278 FLD<> S 1≠S 2 S 1=S 2 279 FLD<= S 1≦S 2 S 1>S 2 280 FLD>= S 1≧S 2 S 1<S 2 FLD D200 F1.2 SET Y21