Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 328 Operands S 1 Number of station to be initialized Explanation 1. Before executing the instruction, be sure to set M1614 to ON to enable Delta servo drive function. ASDA-A2 is available for DVP-ES2 with firmware V3.48 or later; for ASDA-A3, it is available for DVP-ES2 with firmware V3.60 or later. After the mode is changed, you need to restart the PLC to activate the setting. 2. It is not available for pulse type instructions. Do not use pulse type contact. 3. The servo range of S is K1–K8. When the input value is greater than 8, PLC will automatically process 8 as the value of S for the initialization.

The station address must start at 1 and the following addresses cannot be skipped or reserved. For example, if S 1 is set to K4, this instruction initializes K1 to K4. 4. Once the instruction is executed, M1615 will be set to OFF. After execution is done, M1615 will be set to ON. 5. Any error occurs during operation, M1616 will be set to ON and the servo drive number that shows error will be stored in D6000, error codes in D6001 and STEP that when error occurs in D6002. 6. Added the heartbeat function for firmware V3.60 or later.

If a heartbeat error (M1067 = ON, D1067 = 0x1901~0x1908; the last 2 codes are the slave ID) occurs after the initialization is complete and the M1617 is OFF (default, indicating when one goes down, all the drivers are 3-540 Mnemonic Operands Function Controllers ES2-C INITC S 1 Initialization for Delta servo drive communication Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F INITC: 3 steps S 1 * * PULSE 16-bit 32-bit -- ES2-C -- M1614 ON: Delta servo drive function OFF: CANopen DS301 mode