Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 330 Operands S 1 : Station address of driver S 2 : Acceleration time (ms) S 3 : Deceleration time (ms) Explanation 1. The INITC instruction must be complete before this instruction is executed. 2. It is not available for pulse type instructions. Do not use pulse type contact. 3. The range of S 1 is K1–K8 (for servo). There will be no execution when the input value is out of the range. 4. Setting range of S 2 and S 3 is 1-32767, any value exceeding this range is treated as 1. (unit: ms) 5. S 2 : Acceleration time is the period of time during which the servo spins up from 0 to 3000.0 rpm. S 3 :

Deceleration time is the period of time during which the servo spins down from 3000.0 rpm to 0. 6. Once the instruction is executed, M1615 will be set to OFF. After execution is done, M1615 will be set to ON. 7. Any error occurs during operation, M1616 will be set to ON and the servo drive number that shows error will be stored in D6000, error codes in D6001 and STEP that when error occurs in D6002. 3-546 Mnemonic Operands Function Controllers ES2-C CASD S 1,S 2,S 3 Set acceleration time and deceleration time for driver Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F CASD: 7 steps S 1 * * S 2 * * * S 3 * * * PULSE 16-bit 32-bit -- ES2-C --