Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Operands S 1 : Station address of a driver S 2 Target speed Explanation 1. The INITC and ASDON (Servo ON) instructions must be complete before this instruction is executed. 2. It is not available for pulse type instructions. Do not use pulse type contact. 3. The range of S 1 is K1–K8 (for servo). There will be no execution when the input value is out of the range. 4. The range of S 2 is -60000 to +60000. The +/- sign indicates the forward / reverse direction. The target position is a relative position. 5. You need to use CASD instruction for acceleration and deceleration. 6. Each ID has an independent flag to decelerate to stop. (M1632-M1639). 7.

Each ID has a corresponding register (D6032-D6047) to store the current position. 8. Any error occurs during operation, M1616 will be set to ON and the servo drive number that shows error will be stored in D6000, error codes in D6001 and STEP that when error occurs in D6002. 9. For corresponding SM and SR of the axes, refer to the DRVIC instruction (API331). 3-555 Mnemonic Operands Function Controllers ES2-C D PLSVC S 1,S 2 Driver speed control Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F PLSVC: 5 steps DPLSVC: 9 steps S 1 * * S 2 * * * PULSE 16-bit 32-bit ES2-C ES2-C