Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming The value of S 3 is in the range of 1~100. 5. For the index addresses and subindex addresses of Delta servo and AC motor drive, refer to the explanation of the COPRW instruction. In principle, the parameter values of Delta servo and AC motor drive are both16-bit or 32-bit values including floating point numbers. If you need write an 8-bit value, use the COPRW instruction. 6. D is the communication completion flag. D will turn on after the sending of multiple communication messages is complete. See the detailed sending process and sequence diagram below.  The COPWL instruction is enabled and starts to send data.

 After the COPWL instruction sends one piece of message, the next PLC instruction continues to execute.  As the COPWL instruction is scanned once again and the prior message has been received by the slave, the COPWL instruction sends the next message.  When the last written-data sending is done, the instruction will set the completion flag to ON.  When the completion flag turns on, the COPWL instruction need be disabled by manual so that the subsequent COPWL or COPRW instruction can continue to work. Note: When you disable the instruction, the completion flag will be automatically cleared accordingly. enable enable COPWL      S 2 2 1 3  1  D  Note:

The sequence diagram above shows the sending of 3 pieces of written data. 7. After the instruction is enabled, wait until the writing is complete and then disable the instruction. 3-562 (Writes 32-bit values) 2 D14 D15 D16, D17 3 D18 D19 D20, D21 disable disable