DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 3-568 Value S receiving mode 2 Description of Remark in S2 S2+1 0 After the sending is complete, no receiving is allowed and a completion flag will be set to ON. Unused Client Mode 0 cannot be set in the sending data length S . 4 1 Complete the sending first, and then start receiving. After receiving is complete, a completion flag will be set to ON. Receiving timeout setting; unit: 1ms; setting range: 100~32000 Client Mode A. 0 cannot be set in the sending data length S . (before 4 firmware V1.90 for DVP12SE) B. 0 can be set in the sending data length S and that 4 indicates not sending but start to receive data.
(available for ES2-E with firmware V1.2, or later, 12SE with firmware V1.92 or later, and 26SE with firmware V2.00 or later) 2 Complete the receiving first, after the receiving is done, send the packets. After the sending is complete, a completion flag will be set to ON. Receiving timeout setting; unit: 1ms; setting range: 100~32000; when the setting value is 0, it means no timeout. Server Mode 0 cannot be set in the sending data length S . 4 3 When the receiving time is less than setting value in S 2+1, after receiving the communication packet, the receiving is complete. Receiving timeout setting; unit: 1ms; setting range: 100~32000; when the setting value is 0, it means no timeout.
Server Mode S is invalid in this mode. 4