3. Instruction Set Target port descriptions: S 2 and S 1 +0, S 1 +1, S 1 +2, S 1 +3 4. The operand S 3 and S 4 specify source data registers and data length. For example : S 3 specifies D150 and the value in S 4 is 10. The instruction ETHRS will send 10 bytes of data, starting from the low byte in D150, D151, D152 and so on. Users can use the instruction DTM to transform 16-bit data into 8-bit data when the transformation is required. The setting range for S 4 is 1~200 words. If the setting values exceed the setting range, the system will use the minimum (1) or the maximum (200) to operate. 5. The operand D 1 specifies a destination data register.
For example, D specifies D10 and D10 is the received data length; the unit is byte. The data received will be stored starting from D11, low byte in D11, D12, D13 and so on. The maximum receiving data length is 200 words; data 3-569 Start Mode Remote IP Local Remote Description communication communication port port 0,1 Specific IP address 0 0 Illegal 0,1 Specific IP address 0 Not equal to 0 Master mode, Specifies the IP address; but not specify the local communication port.
0,1 Specific IP address Not equal to 0 0 Illegal 0,1 Specific IP address Not equal to 0 Not equal to 0 Master mode, Specifies the IP address, local communication port and remote communication port 0,1 0.0.0.0 No limit to the value No limit to the value Illegal 2,3 Specific IP address 0 No limit to the value Illegal 2,3 Specific IP address Not equal to 0 0 Slave mode, Not specify the IP address and remote communication port 2,3 Specific IP address Not equal to 0 Not equal to 0 Slave mode, Specify the IP address and remote communication port 2,3 0.0.0.0 0 No limit to the value Illegal 2,3 0.0.0.0 Not equal to 0 0 Slave mode, Not specify the IP address and remote communication port 2,3 0.0.0.0 Not equal to 0 Not equal to 0 Slave mode, Not specify the IP address and remote communication port 2,3 Specific IP address 0 No limit to the value Illegal