DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming length exceeds this limit will not be stored in D . Users can use the instruction DTM to transform 16-bit data into 8-bit data when the transformation is required. 6. D 2 specifies the reception completion flag and only M device can be used. When the instruction is executed, and the transmission of packets is complete, this flag will be set to ON. Users can learn from this flag to see if the transmission is complete or not. Once it is set to ON, users need to set it to OFF. When there is any error occurred during the instruction execution or any timeout occurred, the flag will not be ON. 7.
Once the instruction is executed, the communication begins. There is no need to use any special flag to trigger the sending. When the instruction is executed, there will be a special M shown to indicate the execution. 8. There is no limitation on the times of using this instruction in the program. However, only one instruction can be executed at a time. 9. When the instruction is forcedly stopped, the communication will also be stopped. And the 10. When this instruction is executed, do not use the Online Mode; otherwise errors may occur completion flag D 2 will not be ON. when receiving and storing data. 11. This instruction is available for the following models and firmware versions. 12.
Relative special flags and registers for the instruction ETHRS: 3-570 12SA2/ Series ES2-E 12SE 26SE 28SA2 SX2 Firmware V1.08 V3.00 V1.88 V2.0 V3.0 version Item Function Defaults StopRun Attributes M1196 ON: the connection of the self-defined Ethernet communication port is enabled. When the instruction ETHRS stops, the connection will still be kept. ON=> OFF: the connection will be disabled. Off: use the instruction ETHRS to control the connection, when the instruction is executed, the connection is enabled. Off Off R/W M1197 ON: the instruction ETHRS is being executed. Off Off R M1198 ON:
when there is a communication error or a communication timeout, the control on the connection of the self-defined Ethernet communication port is through M1196. When the communication timeout occurs, Off Off R/W