DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 4.1 Communication Ports DVP-ES2/EX2/SA2/SE/SX2 offers 3 communication ports (COM1~COM3), and DVP-SS2 offers 2 COM ports (COM1~COM2). COM ports of the above models support DELTA Q-link communication format on HMI. Refresh rate of HMI can be increased by this function. COM1: RS-232 communication port. COM1 can be used as master or slave and is the major COM port for PLC programming. (It is not applicable to DVP-SE.) COM2: RS-485 communication port. COM2 can be used as master or slave. COM3 (ES2/EX2/SA2/SE): RS-485 communication port. COM3 can be used as master or slave. (For DVP-ES2-C, COM3 is the CANopen port.) COM3 (SX2):
Conversion from the USB port to RS-232 port. COM3 can be used as slave only. The 3 COM ports on the models mentioned above support Modbus ASCII or RTU communication format. USB (COM1) (SE): USB communication port. It only can be used as a slave. The communication mode and format can not be modified. Communication Format:
4-2 COM port RS-232 RS-485 RS-485 RS-485 Parameter (COM1) (COM2) (COM3) (SX2 COM3) 110~115200 bps 110~921000 bps 110~115200 bps Baud rate 7~8bits Data length Even / Odd / None parity check Parity 1~2 bits Length of stop bit D1036 D1120 D1109 Register for Setting Retain communication M1138 M1120 M1136 format Available for both Master/Slave Available for Slave ASCII mode Available for both Master/Slave Available for Slave RTU mode ASCII/RTU mode M1139 M1143 M1320 selection Communication address D1121 D1255 of Slave Data length for access 100 registers (ASCII)