Delta DVP-ES2 — 4.2.1 ADR (Communication Address)

4. Communications Default communication settings for all COM ports: − Modbus ASCII − 7 data bits − 1 stop bit − Even parity − Baud rate: 9600 4.2 Communication Protocol ASCII mode Communication Data Structure 9600 (Baud rate), 7 (data bits), Even (Parity), 1 (Start bit), 1 (Stop bit) Corresponding table for Hexadecimal value and ASCII codes 4.2.1 ADR (Communication Address) Valid communication addresses are in the range of 0~254. Communication address equals to 0 means broadcast to all PLCs. PLC will not respond to a broadcast message. PLC will reply a normal message to the master device when communication address is not 0.

4-3 COM port RS-232 RS-485 RS-485 RS-485 Parameter (COM1) (COM2) (COM3) (SX2 COM3) Data length for access 100 registers (RTU) Field name Content Explanation Start bit STX Start bit ‘:’ (3AH) Communication address ADR 1 Address consists of 2 ASCII codes ADR 0 Command code CMD 1 Command code consists of 2 ASCII codes CMD 0 Data DATA (0) Data content consist of 2n ASCII codes, n≤205 DATA (1) ……….

DATA (n-1) LRC checksum LRC CHK 1 LRC checksum consists of 2 ASCII codes LRC CHK 0 Stop bit END1 Stop bit consists of 2 ASCII codes END1 = CR (0DH), END0 = LF (0AH) END0 ASCII “0“ “1“ “2“ “3“ “4“ “5“ “6“ “7“ Hex 30H 31H 32H 33H 34H 35H 36H 37H ASCII “8“ “9“ “A“ “B“ “C“ “D“ “E“ “F“ Hex 38H 39H 41H 42H 43H 44H 45H 46H