DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 4.5 Command Code 4.5.1 Command Code: 01, Read Status of Contact (Input point X is not included) Number of Points (max) = 255 (Dec) = FF (Hex) Example : Read contacts T20~T56 from Slave ID#1 PC → PLC “:01 01 06 14 00 25 BF CR LF” Sent message:
4-12 Effective Range MODBUS Device Range SA2/SE Address ES2/EX2 SS2 Address SX2 D 6144~6399 0000 ~ 9999 N/A 0000 ~ 9999 436865~440960 9800~98FF D 6400~6655 9900~99FF D 6656~6911 9A00~9AFF D 6912~7167 9B00~9BFF D 7168~7423 9C00~9CFF D 7424~7679 9D00~9DFF D 7680~7935 9E00~9EFF D 7936~8191 9F00~9FFF D 8192~8447 440961~442768 A000~A0FF D 8448~8703 A100~A1FF D 8704~8959 A200~A2FF D 8960~9215 A300~A3FF D 9216~9471 A400~A4FF D 9472~9727 A500~A5FF D 9728~9983 A600~A6FF D 9984~9999 A700~A70F D 10000~11999 Applicable to DVP-SE 442769~444768 A710~AEDF Field Name ASCII STX :
Slave Address 01 Command code 01 Starting Address Hi 06 Starting Address Lo 14 Number of Points Hi 00 Number of Points Lo 25 Error Check (LRC) BF ETX 1 0D (Hex) ETX 0 0A (Hex)