4. Communications Assume Number of Points in sent message is n (Dec), quotient of n /8 is M and the remainder is N. When N = 0, Bytes Count in feedback message will be M ; when N ≠ 0, Bytes Count will be M+1 . PLC → PC “:01 01 05 CD 6B B2 0E 1B D6 CR LF” Feedback message: 4.5.2 Command Code: 02, Read Status of Contact (Input point X is included) Example: Read status of contact Y024~Y070 from Slave ID#01 PC → PLC “: 01 02 05 14 00 25 BF CR LF” Sent message: Assume Number of Points in sent message is n (Dec), quotient of n /8 is M and the remainder is N. When N = 0, Bytes Count in feedback message will be M ; when N ≠ 0, Bytes Count will be M+1 . PLC → PC “:
01 01 05 CD 6B B2 0E 1B E5 CR LF” Feedback message: 4-13 Field Name ASCII STX : Slave Address 01 Command code 01 Bytes Count 05 Data (Coils T27…T20) CD Data (Coils T35…T38) 6B Data (Coils T43…T36) B2 Data (Coils T51…T44) 0E Data (Coils T56…T52) 1B Error Check (LRC) E6 END 1 0D (Hex) END 0 0A (Hex) Field Name ASCII STX : Slave Address 01 Command code 02 Starting Address Hi 05 Starting Address Lo 14 Number of Points Hi 00 Number of Points Lo 25 Error Check (LRC) BF END 1 0D (Hex) END 0 0A (Hex) Field Name ASCII STX : Slave Address 01 Command code 02