Delta DVP-ES2 — 4.5.3 Command Code: 03, Read Content of Register (T, C, D)

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 4.5.3 Command Code: 03, Read Content of Register (T, C, D) Example: Read coils T20~T27 from Slave ID#01 PC → PLC “: 01 03 06 14 00 08 DA CR LF” Sent message: PLC → PC “:01 03 10 00 01 00 02 00 03 00 04 00 05 00 06 00 07 00 08 B8 CR LF” Feedback message: 4-14 Field Name ASCII Bytes Count 05 Data (Coils Y033…Y024) CD Data (Coils Y043…Y034) 6B Data (Coils Y053…Y044) B2 Data (Coils Y063…Y054) 0E Data (Coils Y070…Y064) 1B Error Check (LRC) E5 END 1 0D (Hex) END 0 0A (Hex) Field Name ASCII STX :

Slave Address 01 Command code 03 Starting Address Hi 06 Starting Address Lo 14 Number of Points Hi 00 Number of Points Lo 08 Error Check (LRC) DA END 1 0D (Hex) END 0 0A (Hex) Field Name ASCII STX : Slave Address 01 Command code 03 Bytes Count 10 Data Hi (T20) 00 Data Lo (T20) 01 Data Hi (T21) 00 Data Lo (T21) 02 Data Hi (T22) 00 Data Lo (T22) 03 Data Hi (T23) 00 Data Lo (T23) 04 Data Hi (T24) 00