4. Communications 4.5.4 Command Code: 05, Force ON/OFF single contact The Force data FF00 (Hex) indicates force ON the contact. The Force data 0000 (Hex) indicates force OFF the contact. Also, When MMNN = 0xFF00, the coil will be ON, when MMNN = 0x0000, the coil will be OFF. Other force data is invalid and will not take any effect. Example: Force coil Y0 ON PC → PLC “: 01 05 05 00 FF 00 F6 CR LF” Sent message: PLC → PC “: 01 05 05 00 FF 00 F6 CR LF” Feedback message: 4-15 Field Name ASCII Data Lo (T24) 05 Data Hi (T25) 00 Data Lo (T25) 06 Data Hi (T26) 00 Data Lo (T26) 07 Data Hi (T27) 00 Data Lo (T27) 08 Error Check (LRC) C8 END 1 0D (Hex) END 0 0A (Hex) Field Name ASCII STX :
Slave Address 01 Command code 05 Coil Address Hi 05 Coil Address Lo 00 Force Data Hi FF Force Data Lo 00 Error Check (LRC) F6 END 1 0D (Hex) END 0 0A (Hex) Field Name ASCII STX : Slave Address 01 Command code 05 Coil Address Hi 05 Coil Address Lo 00 Force Data Hi FF Force Data Lo 00 Error Check (LRC) F6 END 1 0D (Hex) END 0 0A (Hex)