Delta DVP-ES2 — 4.5.6 Command Code: 15, Force ON/OFF multiple contacts

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 4.5.5 Command Code: 06, Set content of single register Example: Set content of register T0: 12 34 (Hex) PC → PLC “: 01 06 06 00 12 34 AD CR LF” Sent message: PLC → PC “: 01 06 06 00 12 34 AD CR LF” Feedback message: 4.5.6 Command Code: 15, Force ON/OFF multiple contacts Max contacts/coils available for Force ON/OFF: 255 Example: Set Coil Y007…Y000 = 1100 1101, Y011…Y010 = 01. PC → PLC “: 01 0F 05 00 00 0A 02 CD 01 11 CR LF” Sent message: 4-16 Field Name ASCII STX :

Slave Address 01 Command code 06 Register Address Hi 06 Register Address Lo 00 Preset Data Hi 12 Preset Data Lo 34 Error Check (LRC) AD END 1 0D (Hex) END 0 0A (Hex) Field Name ASCII STX : Slave Address 01 Command code 06 Register T0 Address Hi 06 Register T0 Address Lo 00 Preset Data Hi 12 Preset Data Lo 34 Error Check (LRC) AD END 1 0D (Hex) END 0 0A (Hex) Field Name ASCII STX : Slave Address 01 Command code 0F Coil Address Hi 05 Coil Address Lo 00 Quantity of Coils Hi 00 Quantity of Coils Lo 0A