Delta DVP-ES2 — 5.3 The Operation of STL Program

5. Sequential Function Chart 3. Designate which step will take over the control from the current step Example: When X0 = ON, S20 = ON, S10 = OFF . Explanation: When S10 = ON, Y0 and Y1 will be ON. When X0 = ON, S20 will be ON and Y20 will be ON. When S10 = OFF, Y0 will be OFF but Y1 will still be ON (SET instruction is applied on Y1, so Y1 will be ON and latched.) STL Transition: When step point Sn is ON, its following output circuit will be activated. When Sn = OFF, its following output circuit will be OFF. The interval between the activation of the step point and its following output circuit is one scan cycle. Repeated Usage of Output Coil: 1.

Output coils of the same number could be used S10 in different step points. 2. See the diagram opposite. There can be the same output device (Y0) among different steps S20 transfers to S20. (sequences). Y0 remains ON when S10 S X1 Y0 3. Y0 will be OFF due to the transition from S10 to S20. However when S20 is ON, Y0 will be ON again. Therefore in this case, Y0 remains ON when S10 transfers to S20. 4. For general ladder diagrams, repeated usages of output coils should be avoided. The No. of output coil used by a step should also avoid being used when the step ladder diagram returns to a general ladder diagram.

5-5 S10 S Y0 SET Y1 X0 SET S20 S20 S Y20 X1 SET S30 SET S30 S10 S Y0 SET Y1 X0 SET S20 S20 S Y20 X1 SET S30 SET S30 SET Y1 SET Y1 SET S20 SET S20 10 Y0 SET Y1 X0 SET S20 SET S20 SET Y1 SET S30