DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Repeated usage of timer: See the opposite diagram. Timers can only be used repeatedly in non-adjacent steps. S20 X1 S30 X2 S40 Transfer of Step Points: SET Sn and OUT Sn instructions are used to enable (or transfer to) another step. Because there can be many step control sequences (i.e. the initial steps starting with S0 ~ S9) existing in the program. The transfer of a step can take place in the same step sequence, or be transferred to different step sequence. Usages of SET Sn and OUT Sn are different according to the transfer methods. Please see the explanations below SET Sn 1. Used for driving the next step in the same sequence.
After the transition, all output in the previous step will be OFF. S10 X0 Y0 When SET S12 executes, S10 transfers to S12 and output Y10 in S10 will be OFF. S12 Y1 X1 2. If M1014 is used, and it is On, the transfer of the steps will be prohibited, and the states of the steps remain unchanged. S10 S Y10 X0 If M1040 is On, SET S12 instruction will not be executed, the state of S 10 unchanged, and Y10 will be On. S12 S Y11 X1 5-6 TMR T1 K10 TMR T2 K20 TMR T1 K30 SET S12 SET S14 SET S12 SET S14