5. Sequential Function Chart 5.6 IST Instruction 60 Operands: S : Source device for assigning pre-defined operation modes (8 consecutive devices). D 1 The smallest No. of step points in auto mode. D 2 : The greatest No. of step points in auto mode. Explanations: 1. The IST is a handy instruction specifically for the initial state of the step ladder operation modes. 2. The range of D 1 and D 2 : S20~S911, D 1 D 2 . 3. IST instruction can only be used one time in a program. Program Example 1: M1000 1. Operation mode: S: X20: Individual operation (Manual operation) X24: Continuous operation X21: Zero return X25: Zero return start switch X22: Step operation X26: Start switch X23:
One cycle operation X27: Stop switch 2. When IST instruction is executed, the following special auxiliary relays will be assigned automatically. M1040: Movement inhibited S0: Manual operation/initial state step point M1041: Movement start S1: Zero point return/initial state step point M1047: STL monitor enable M1042: Status pulse S2: Auto operation/initial state step point 3. When IST instruction is used, S10~S19 are occupied for zero point return operation and cannot be used as a general step point. In addition, when S0~S9 are in use, S0 initiates “manual operation mode”, S1 initiates “zero return mode” and S2 initiates “auto mode”.
Thus, the three step points of initial state have to be programmed in first priority. 4. When S1 (zero return mode) is initialized, i.e. selected, zero return will NOT be executed if any of the state S10~S19 is ON. 5-23 Mnemonic Operands Function Controllers ES2/EX2 SS2 SA2 SX2 Controllers ES2/EX2 SS2 SA2 SX2 IST Initial State Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F IST: 7 steps S * * * D 1 * D 2 * PULSE 16-bit 32-bit ES2/EX2 SS2 SA2 SX2 ES2/EX2 SS2 SA2 SX2 ES2/EX2 SS2 SA2 SX2 IST X20 S20 S60