DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 6.3 Error Detection Devices 6-6 Error code Description Action C40D Use I / P incorrectly instructions is incorrectly specified.
Select programming mode and correct the identified error C40E IRET doesn’t follow by the last FEND instruction SRET doesn’t follow by the last FEND instruction C40F PLC program and data in parameters have not been initialized C41B Invalid RUN/STOP instruction to extension module C41C The number of input/output points of I/O extension unit is larger than the specified limit C41D Number of extension modules exceeds the range C41F Failing to write data into memory C440 Hardware error in high-speed counter C441 Hardware error in high-speed comparator C442 Hardware error in MCU pulse output C443 No response from extension unit C450 The analog-to-digital/digital-to-analog function of the MCU fails.
C4EE No END command in the program C4FF Invalid instruction (no such instruction existing) C430 Error occurs while the left-side module is being initialized Replace with a new module C437 Error occurs while checking the memory of the left-side module C438 Error occurs while checking the model code of the left-side module Error Check Description Drop Latch STOP RUN RUN STOP Devices M1067 Program execution error flag None Reset Latch M1068 Execution error latch flag None Latch Latch D1067 Algorithm error code None Reset Latch D1068 Step value of algorithm errors None Latch Latch Device D1067 Description Error Code 0E18 BCD conversion error 0E19 Division error (divisor=0) 0E1A Floating point exceeds the usage range 0E1B The value of square root is negative