7 CANopen Function and Operation If the CAN port functions as a slave, it has the following functions. It supports the standard CANopen protocol DS301 V4.02. It supports the NMT (network management object) service. It supports the NMT state control. The state of DVP-ES2-C in the CANopen network is controlled by a master. It supports the NMT error control. Heartbeat is supported, but Node Guarding is not supported. It supports the PDO (process data object) service. The PDO message is used to transmit the immediate input data and output data. It supports 8 TxPDO at most, and 8 RxPDO at most. The PDO transmission type:
The synchronous mode, and the asynchronous mode It supports the emergency service. If an error or an alarm occurs in DVP-ES2-C, the master is notified through the emergency. 7.1.2 The Input/Output Mapping Areas DVP-ES2-C as a master supports 16 slaves at most, and the slave node ID range from 1 to 16. The output mapping areas are D6250-D6476, and the input mapping areas are D6000-D6226. If DVP-ES2-C functions as a slave station, the output mapping areas are D6282-D6313, and the input mapping areas are D6032-D6063.
7.2 The Installation and the Network Topology This section introduces the dimensions of DVP-ES2-C, the CAN interface, the CANopen network framework, and the communication distance. 7.2.1 The Dimensions 106 110 L1 61.5 L 78 Unit: millimeter 7-3 Mapping Device in the PLC Mapping area length SDO reque D6250~D6281 Emergency st information, NMT service information, and request information 64 bytes SDO reply i D6000~D6031 information nformation, and Emergency reply 64 bytes D6282~D6476 RxPDO ma pping area 390 bytes D6032~D6226 TxPDO ma pping area 390 bytes Mapping Device in the PLC Mapping area length D6032~D6063 RxPDO ma pping area 64 bytes D6282~D6313 TxPDO ma pping area 64 bytes 90 98