Delta DVP-ES2 — 7.2.3 The CAN Interface and the Network Topology

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming  The topology structure of the CANopen network 1) Users should use standard Delta cables when creating the CANopen network. These cables are the thick cable UC-DN01Z-01A (TAP-CB01), the thin cable UC-DN01Z-02A (TAP-CB02), and the thin cable UC-CMC010-01A (TAP-CB10). The communication cables should be away from the power cables. 2) TAP-TR01. CAN+ and CAN-, which are at the endpoints of the network, should be connected to 120 ohm resistors. Users can purchase the standard Delta terminal resistor TAP-TR01.

3) The limitation on the length of the CANopen network The transmission distance of the CANopen network depends on the transmission rate of the CANopen network. The relation between the transmission rate and the maximum communication distance is shown in the following table. 4) The Delta network products related to the CANopen network are listed below. 7-6 Transmission rate 20K 50K 125K 250K 500K 1M (bit/second) Maximum 2500 1000 500 250 100 25 communication distance (meter) Product Model Function DVP32ES200RC DVP32ES200TC It is a DVP-ES2-C series PLC with the built-in CAN interface. It can function as the CANopne master or slave.