DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Heartbeat consumer Request Reuqest Heartbeat timeout period Heartbeat evnet Boot-up services After the slave completes the initialization and enters the pre-operational state, it transmits the Boot-up message. Other predefined CANopen communication objects (SYNC and EMCY) SYNC Object (Synchronous object) The synchronous object is the message broadcasted periodically by the master node in the CANopen network. This object is used to realize the network clock signal. Every device decides whether to use the event and undertake the synchronous communication with other network devices according to its configuration.
For example, when controlling the driving device, the devices do not act immediately after they receive the command sent by the master. They do act until they receive the synchronous message. In this way, many devices can act synchronously. The format of the SYNC message: COB-ID 80 (hex) Emergency object The emergency object is used by the CANopen device to indicate an internal error. When an emergency error occurs in the device, the device sent the emergency message (including the emergency error code), and the device enters the error state. After the error is eliminated, the device sends the emergency message, the emergency error code is 0, and the device enters the normal state.
The format of the emergency message: Note: The value in the error register is mapped to index 1001 (hex) in the object dictionary. If the value is 0, no error occurs. If the value is 1, a normal error occurs. If the value is H’80, an internal error occurs in the device. 7-14 Heartbeat producer Receiving Receivin Receivin g Receiving Heartbeat timeout period artbeat Heartbeat producing time COB-ID Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 80 (hex) +Node-ID Emergency error code Error register Factory-defined error code LSB MSB