7 CANopen Function and Operation 7.3.3 The Predefined Connection Set In order to decrease the configuration workload of the network, CANopen defines a default identifier. In the predefine connection set, the structure of the 11-bit identifier is as follows. Function code Node ID The objects which are supported and the COB-IDs which are assigned to the objects are listed below.
The broadcast object in the predefined connection setting The corresponding object in the predefined connection set 7.4 Sending SDO, NMT and Reading Emergency Message through the Ladder Diagram Editing the request message mapping area can realize the transmission of SDO, NMT and Emergency message.The corresponding relations between the request message mapping area, response message mapping area and PLC device are shown below. 1> CANopen master can only send one SDO, NMT or Emergency request message to the same equipment at a time. 2> We suggest the request message mapping area should be cleared to zero when sending SDO, NMT or Emergency request message through WPL program.
7-15 Index of the Object Function code COB-ID communication parameter NMT 0000 0 - SYNC 0001 128 (80h) 1005h, 1006h, 1007h Time stamp 0010 256 (100h) 1012h, 1013h Index of the Object Function code COB-ID communication parameter Emergency 0001 129 (81h)–255 (FFh) 1014h, 1015h PDO1 (TX) 0011 385 (181h)–511 (1FFh) 1800h PDO1 (RX) 0100 513 (201h)–639 (27Fh) 1400h PDO2 (TX) 0101 641 (281h)–767 (2FFh) 1801h PDO2 (RX) 0110 769 (301h)–895 (37Fh) 1401h PDO3 (TX) 0111 879 (381h)–1023 (3FFh) 1802h PDO3 (RX) 1000 1025 (401h)–1151 (47Fh) 1402h PDO4 (TX) 1001 1153 (481h)–1279 (4FFh) 1803h PDO4 (RX) 1010 1281 (501h)–1407 (57Fh) 1403h SDO (TX) 1011 1409 (581h)–1535 (5FFh) 1200h SDO (RX) 1100 1537 (601h)–1663 (67Fh) 1200h NMT Error Control 1110 1793 (701h)–1919 (77Fh) 1016h, 1017h PLC device Mapping area Mapping length D6250~D6281 SDO request message, NMT service message and Emergency request message 64 bytes D6000~D6031 SDO response message and Emergency response message 64 bytes