DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming B.2.3 DVPEN01-SL (Left-side Ethernet Communication Module) B-4 CR number Attribute Register name Description HW LW #113~#96 - Reserved #114 R/W MPDBUS TCP time-out Setting up MODBUS TCP time-out (in ms) Default:
3000 #115 R/W MODBUS TCP trigger Setting up whether to send out data in MODBUS TCP mode #116 R/W MODBUS TCP status Displaying current status of MODBUS TCP mode #118 #117 R/W MODBUS TCP destination IP Setting up destination IP address for MODBUS TCP transaction #119 R/W MODBUS TCP data length Setting up the data length for MODBUS TCP transaction #219~#120 R/W MODBUS TCP data buffer Data buffer of MODBUS TCP for storing sending/receiving data #248~#220 - Reserved #249 R Sub-version #250 R Update date 0xC820 (April 8, 2012) #251 R Error code Displaying the errors. See the error code table for more information.
#255~#252 - Reserved Symbols “R” refers to “able to read data by FROM instrcution”; “W” refers to “able to write data by TO instrcution”. DVPEN01-SL Ethernet communication module CR number Attribute Register name Description HW LW #0 R Model name Set up by the system; read only. Model code of DVPEN01-SL = H’4050 #1 R Firmware version Displaying the current firmware version in hex. #2 R Communication mode b0: MODBUS TCP mode b1:
data exchange mode #3 W E-Mail Event 1 trigger Set up whether to send E-Mail 1 #4 W E-Mail Event 2 trigger Set up whether to send E-Mail 2 #5 W E-Mail Event 3 trigger Set up whether to send E-Mail 3 #6 W E-Mail Event 4 trigger Set up whether to send E-Mail 4 #7 R Status of E-Mail 1, 2 b0 ~ b7: Current status of E-Mail 2 b8 ~ b15: Current status of E-Mail 1 #8 R Status of E-Mail 3, 4 b0 ~ b7: Current status of E-Mail 4 b8 ~ b15: Current status of E-Mail 3 #9 R/W E-Mail 1 additional message Filled in by the user, and it will be sent by E-mail. #10 R/W E-Mail 2 additional message Filled in by the user, and it will be sent by E-mail.
#11 R/W E-Mail 3 additional message Filled in by the user, and it will be sent by E-mail. #12 R/W E-Mail 4 additional message Filled in by the user, and it will be sent by E-mail. #13 R/W Data exchange trigger Set up whether to send out data in data exchange mode #14 R Status of data exchange Displaying current status of data exchange. #15 R/W Enabling flag for RTU mapping 1: Enable; 0: Disable. Default = 0 #16 R/W Connection status of RTU mapping slave b0: Status of RTU slave 1 b1: Status of RTU slave 2 b2: Status of RTU slave 3 b3: Status of RTU slave 4