Delta DVP-ES2 — B.2.3 DVPEN01-SL (Left-side Ethernet Communication Module)

Appedndix B Setting and Using an Ethernet PLC/Module B-5 DVPEN01-SL Ethernet communication module CR number Attribute Register name Description HW LW #17 R/W Data exchange cycle time The control register is used to set data exchange cycle time. The unit used is a millisecond. #19 #18 R Error status of slaves in data exchange 0: No error occurs. 1: An error occurs in data exchange. b0~b15 in CR#19: States of slave 1~slave 16. b0~b8 in CR#18: States of slave 17~slave 24. #24~#20 - Reserved #26 #25 R/W Destination IP Destination IP address for data exchange #27 R/W Function code for a data exchange mode 0: The function code for the reading of data and the writing of data is “17”. 1:

The function codes for the reading of data is “03, the function code for the writing of a single piece of data is “06”, and the function code for the writing of multiple pieces of data is “10”.

#28 R/W Destination Slave ID Destination Slave ID for data exchange #48~#29 R/W Data transmission buffer Buffer for transmitted data in data exchange #68~#49 R Data receiving buffer Buffer for received data in data exchange #80~#69 - Reserved #81 R/W Read address for data exchange Slave transmission buffer address for data exchange #82 R/W Read length for data exchange Number of registers for read data #83 R/W Received address for data exchange Buffer address for the receiving Master in data exchange #84 R/W Written-in address for data exchange Buffer address for the receiving Slave in data exchange #85 R/W Written-in length for data exchange Number of registers for data transmission #86 R/W Transmission address for data exchange Master transmission buffer address for data exchange #87 R/W Mode of setting an IP address 0:

Static IP address 1: DHCP #89 #88 R/W IP address Setting an IP address #91 #90 R/W Netmask Setting a netmask #93 #92 R/W Gateway IP address Setting a gateway IP address #94 R/W Enabling the setting of an IP address Executing the setting of an IP address #95 R Status of setting an IP address Showing the status of setting an IP address 0: The setting of an IP address is successful. 1: The setting of an IP address fails. #101~#96 - Reserved #102 R/W MC Protocol UDP port Setting the UDP port of an MC protocol data exchange slave (Default value:

1025) #110~#103 - Reserved #111 R/W 8-bit processing mode Setting up MODBUS TCP Master control as 8-bit mode #112 R/W MODBUS TCP Keepalive time MODBUS TCP Keepalive time (Unit: Second) #113 - Reserved #114 R/W MODBUS TCP timeout Setting up MODBUS TCP timeout (Unit: Millisecond)