DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming (3) Error codes B.5.2 EtherNet/IP Objects Supported by DVP-SE / ES2-E Series PLCs (1) Identity Object (0x01) Instance: 0x01 (2) Message Router (0x02) Instance: 0x01 (3) Assembly (0x04) Explicit message DVP12SE: Conformance Test is not supported. B-14 Value Name Description 0 Success Success 0x01 Connection Failure The forwarding function can not be enabled. 0x04 Path Segment Error The segment type is not supported. (ref. V1 C-1.4) 0x05 Path Destination Unknown The instance is not supported. 0x08 Service Not Supported The service (Get or Set) is not supported. 0x09 Invalid Attribute Value The value written is incorrect.
0x0E Attribute Not Settable The setting of the attribute is not allowed. 0x13 Not Enough Data The length of the data written is too short. 0x14 Attribute Not Supported The attribute is not supported. 0x15 Too Much Data The length of the data written is too long. 0x16 Object Not Exist The object is not supported. 0x20 Invalid Parameter The service parameter is not supported. (ref. V1 5-2.3.1) 0x26 Path Size Invalid Incorrect item length Attribute Name Access Data Type Value 0x01 Vendor ID Get UINT 799 (Delta Electronics, inc.) 0x02 Device Type Get UINT 14 (Programmable Logic Controller) 0x03 Product Code Get UINT Product code 0x04 Revision Get STRUCT of:
Device version; Display as Major.Minor Major USINT Major: 0x01~0x7F Minor USINT Minor: 0x01~0xFF 0x05 Status Get WORD 0 (Owned ) 0x06 Serial Number Get UDINT Serial number: the last 4 digits of the MAC address, ab:cd 0x07 Product Name Get SHORT STRING Module Name 0x08 State Get _ UINT 0x03 (ES2-E & DVP26SE Only) Attribute Name Access Data Type Value 0x02 Number Available Get UINT 0 0x03 Number Active Get UINT 0 Instance Attribute Name Access Data Type Data 0x65 0x66 0x67 0x68 0x69 0x03 D Block 1 Set 10 words D500~D509 D Block 2 Set 30 words D510~D539 D Block 3 Set 60 words D540~D599 D Block 4 Set 100 words D600~D699 D Block 5 Set 100 words D700~D799