Delta DVP-ES2 — B.5.2 EtherNet/IP Objects Supported by DVP-SE / ES2-E Series PLCs

Appedndix B Setting and Using an Ethernet PLC/Module ES2-E & DVP26SE Config Data (4) X input DVP12SE: (0x64) B-15 0x6A D Block 6 Set 100 words D800~D899 0x6B D Block 7 Set 100 words D900~D999 Connection Name Instance Data Length Default No.

Attribute Connection 1 Input 0x65 100 words D0 ~ D99 Output 0x64 100 words D3000 ~ D3099 Configuration 0x80 8 words Refer to Config Data below Connection 2 Input 0x67 100 words D100 ~ D199 Output 0x66 100 words D3100 ~ D3199 Configuration 0x81 8 words Refer to Config Data below Connection 3 Input 0x69 100 words D200 ~ D299 Output 0x68 100 words D3200 ~ D3299 Configuration 0x82 8 words Refer to Config Data below Connection 4 Input 0x6B 100 words D300 ~ D399 Output 0x6A 100 words D3300 ~ D3399 Configuration 0x83 8 words Refer to Config Data below Connection 5 Input 0x6D 100 words D400 ~ D499 Output 0x6C 100 words D3400 ~ D3499 Configuration 0x84 8 words Refer to Config Data below Connection 6 Input 0x6F 100 words D500 ~ D599 Output 0x6E 100 words D3500 ~ D3599 Configuration 0x85 8 words Refer to Config Data below Connection 7 Input 0x71 100 words D600 ~ D699 Output 0x70 100 words D3600 ~ D3699 Configuration 0x86 8 words Refer to Config Data below Connection 8 Input 0x73 100 words D700 ~ D799 Output 0x72 100 words D3700 ~ D3799 Configuration 0x87 8 words Refer to Config Data below Parameter Data Type Data Default Input Device Type INT Input (T to O) device type 0:

D register 0 Input Device Quantity INT Input (T to O) device quantity 100 Input Device Address DINT Input (T to O) device address 0: D0, 1: D1… Refer to Connection 1 ~ 8 Output Device Type INT Output (O to T) device type 0:D register 0 Output Device Quantity INT Output (O to T) device quantity 100 Output Device Address DINT Output (O to T) device address 0: D0, 1: D1… Refer to Connection 1 ~ 8 Instance Attribute Name Access Data Type 1 0x64 X0 Get BYTE 2 0x64 X1 Get BYTE …… 256 0x64 X377 Get BYTE